11 Best Practices to Save on Data Centre Power

Here is Gartner’s list of green IT best practices for data centre managers:

Plug holes in the raised floor: Most raised-floor environments exhibit cable holes, conduit holes and other breaches that allow cold air to escape and mix with hot air. This single low-tech retrofit can save as much as 10 percent of the energy used for data centre cooling.

Install blanking panels: Any unused position in a rack needs to be covered with a blanking panel to manage airflow in a rack by preventing the hot air leaving one piece of equipment from entering the cold-air intake of other equipment in the same rack. When the panels are used effectively, supply air temperatures are lowered by as much as 22 degrees Fahrenheit, greatly reducing the electricity consumed by fans in the IT equipment and potentially alleviating hot spots in the data centre.

Coordinate CRAC units: Older CRAC (computer room air-conditioning) units operate independently with respect to cooling and dehumidifying the air. These units should be tied together with newer technologies so that their efforts are coordinated, or managers should remove humidification responsibilities from them altogether and place those responsibilities on a newer piece of technology.

Improve underfloor airflow: Older data centres typically have constrained space underneath the raised floor that is not only used for the distribution of cold air, but also has served as a place for data cables and power cables. Many old data centre’s have accumulated such a tangle of these cables that airflow is restricted, so the underfloor should be cleaned out to improve airflow.

Implement hot aisles and cold aisles: In traditional data centres, racks were set up in what is sometimes referred to as “classroom style,” where all the intakes face in a single direction. This arrangement causes the hot air exhausted from one row to mix with the cold air being drawn into the adjacent row, thereby increasing the cold-air-supply temperature in uneven and sometimes unpredictable ways. Newer rack layout practices instituted in the past 10 years demonstrate that organising rows into hot aisles and cold aisles is better for controlling the flow of air in the data centre.

Install sensors: A small number of individual sensors can be placed in areas where temperature problems are suspected. Simple sensors store temperature data that can be manually collected and transferred into a spreadsheet, where it can be further analysed. Even this minimal investment in instrumentation can provide great insight into the dynamics of possible data centre temperature problems and can provide a method for analyzing the results of improvements made to data centre cooling.

Page: 1 2

Chris Preimesberger

Editor of eWEEK and repository of knowledge on storage, amongst other things

Recent Posts

Apple, Google Mobile Ecosystems Should Be Investigated, CMA Told

CMA receives 'provisional recommendation' from independent inquiry that Apple,Google mobile ecosystem needs investigation

9 hours ago

Australia Rejects Elon Musk Claim About Social Media Ban For Under-16s

Government minister flatly rejects Elon Musk's “unsurprising” allegation that Australian government seeks control of Internet…

12 hours ago

Northvolt Files For Bankruptcy Protection In US

Northvolt files for Chapter 11 bankruptcy protection in the United States, and CEO and co-founder…

14 hours ago

UK’s CMA Readies Cloud Sector “Behavioural” Remedies – Report

Targetting AWS, Microsoft? British competition regulator soon to announce “behavioural” remedies for cloud sector

1 day ago

Former Policy Boss At X, Nick Pickles, Joins Sam Altman Venture

Move to Elon Musk rival. Former senior executive at X joins Sam Altman's venture formerly…

1 day ago

Bitcoin Rises Above $96,000 Amid Trump Optimism

Bitcoin price rises towards $100,000, amid investor optimism of friendlier US regulatory landscape under Donald…

1 day ago